SC 8.1 GME MONOBLOC gas burner with electronic modulating control BETA series
SC. 8.1 GME |
|||||
---|---|---|---|---|---|
Power | Kw/h | Min | 330 | ||
Max | 1150 | ||||
m3/h | Min | 283.800 | |||
Max | 989.000 | ||||
Supply voltage | 3N-50 Hz 380V | ||||
Engine | 1,5 | ||||
Valve diameter 300 mbar | 1 1/2″ |
Category: Gas Burners
More information
Modulating burners with electronic regulation regulation represent an evolution of the traditional mechanical type adjustment system towards a digital type system.
The servomotors of each of the air, gas and liquid fuel flow adjustment devices respond to orders from a microprocessor in which the parameter curves defined for each of these elements have been recorded.
-
-
- Duoblock burners with high temperature steel housing and combustion head.
- The following fuels may be used:
- Natural gas, PCI 6.99 ... 11.39 kWh/m3;
- LPG, PCI 25.89 kWh/m3
- Biogas
- It is suitable for steam, hot water boiler, furnaces, dryers, thermal oil generators, etc.
- Each burner can be customized to the needs of the installation.
- Digital programming is done on the screen or using a computer, and following the simple instructions.
- The additional advantage offered by the system lies in the precise knowledge of all the commands and all the states of the system as a whole.
- In addition, the microprocessor system also performs the following functions:
- Control and monitoring of the burner start-up and operation phases, with the possibility of configuring the set modes and times;
- The ease of design and the use of preheated combustion air while allowing energy savings by increasing the efficiency of the combustion economizer used by the system.
- Flame control, with different monitoring devices, for intermittent or continuous operation (more than 24 hours);
- Integrated gas valve check system checks for leaks at each burner cycle for added safety
- Up to 15 programmable points for each air-fuel ratio curve
- Access levels are protected by specific passwords corresponding to the different types of users (viewing by customer, programming by technician, etc.).
- The system can be completed by integrating it with an automatic excess air adjustment system by oxygen sensor with action on the position of the air damper.
- Finally, the fan speed adjustment system with variable speed drive to ensure maximum energy savings, both fuel and electrical energy.
- Standard protection of mechanical parts IP 54.
- IP 65 protection on request.
- The flame geometry can be adjusted according to the combustion chamber.
- The modulation ratio is 1/7 and is really advantageous according to our competitors.
- Compliance with the following directives:
- 89/336 (2004/108) EEC
- 73/23/EEC
- 98/37/EEC
- 90/396/EEC
- EN 676
-
OPTIONS
-
- Continuous O2 analyzer to provide extra efficiency.
- Continuous CO analyzer for a sensitive control system.
- Variable speed drive (inverter) to extend product life.
- IP 65 protection on request.
- Possibility to select the premixing head for low NOx.
- Internal or external recirculation of combustion gases for low emissions.
- Simultaneous combustion.
- Soundproof fan.